QJ50 / QJ80 — DN50 / DN80 gas and oil-surge relaysSeries reference image

Buchholz Relays

QJ50 / QJ80

DN50 / DN80 gas and oil-surge relays

Installed between tank and conservator. Gas collection, sampling and signal-memory options are selected in the order code.

Manufacturer: Shenyang Zhiyue Electric Technology Co., Ltd.

Pipe diameterDN50 / DN80
Gas accumulation250–300 mL
Download Datasheet

Gas and oil-surge protection for oil-filled transformers.

  • Sight-glass gas accumulation reading (QJ25: 200–250 mL) for early fault warning.
  • Oil-surge trip at 1.0 ± 0.1 m/s for sudden internal faults.
  • DN25 / DN50 / DN80 coverage across the QJ range.

For power and distribution transformers, including replacement of an existing relay on an installed unit — match by pipe diameter and contact arrangement first.

TECHNICAL DATA

Key specifications

Pipe diameter
DN50 / DN80
Gas accumulation
250–300 mL
Oil velocity setting
Diameter-specific; see table
Operating temperature
−40 to +100 °C
Oil velocity settings
PipeSetting rangeFactory setting
DN500.6–1.2 m/s0.8 ± 0.1 m/s
DN800.7–1.5 m/s1.0 ± 0.1 m/s

Dimensions and contact arrangements vary by configuration. Confirm the complete order code and approved drawing before ordering.

MODEL REFERENCES

Select a model for your inquiry.

Listed models and order-code examples identify configurations within this series.

ENGINEERING REVIEW

Technical documents

AVAILABLE NOW · NO FORM REQUIRED

QJ50 / QJ80 Technical Data

Specifications, mounting dimensions and wiring in one PDF.

3 pages · English text / original bilingual drawings · Rev 1.0
Download PDF

Need a configuration-specific drawing or certificate? Send the exact model and requirements.

Transmission lines crossing a mountain landscape

YOUR PROJECT. OUR ATTENTION TO DETAIL.

Tell us what you need.

Send us the model, specifications or an existing nameplate.
We’ll help confirm the configuration for your project.

TRANSFORMER
PROTECTION
COMPONENTS.